The Megger MIT415/2 is a handheld CAT IV insulation and continuity tester. It’s built for electricians and maintenance technicians testing electrical installations, cables and motors, and for low-voltage work such as ESD, avionics and lift (elevator) control wiring. It combines insulation resistance, continuity and voltage testing in one rugged unit. Low 10 V and 25 V test voltages make it safe for sensitive circuits and signal wiring. A stabilised test voltage gives accurate, repeatable results without the risk of over-voltage damage. The weatherproof over-moulded case makes it suited to work in the field.
Key features:
- Operating temperature: −10 to +55 °C.
- Dimensions: 228 (L) × 108 (W) × 63 (D) mm.
- Weight: 600 g.
- Six insulation test voltages: 10, 25, 50, 100, 250 and 500 V.
- Wide insulation resistance range: From 2 GΩ at 10 V up to 100 GΩ at 500 V.
- Stabilised test voltage: Holds the output within −0% to +2% of the set voltage, which prevents over-voltage damage.
- PI and DAR testing: Polarisation index and dielectric absorption ratio tests for assessing insulation condition, plus timed testing.
- ESD display option: Shows results as powers of ten (10⁵, 10⁶, 10⁷) instead of kΩ, MΩ and GΩ.
- Test lock: Holds the insulation test on for hands-free testing.
- Fast continuity testing: Single auto-range from 0.01 Ω to 1 MΩ, with 200 mA or 20 mA test currents.
- Lead null: Compensates for up to 9 Ω of test lead resistance.
- AC/DC voltage measurement: True RMS up to 600 V AC/DC, with frequency display.
- Live circuit detection: Blocks insulation testing when it detects voltage above a user-set limit (the default is 50 V).
- Analogue arc and dual digital display: Shows the measurement and the actual test voltage at the same time.
- Rugged design: Rubber over-moulded case with a back stand.
- Power: Six AA alkaline or NiMH batteries.
- Supplied with: Silicone test leads with probes and clips, batteries, a hard carry case and an owner’s information CD.
Standards:
- CAT IV 600 V
- IP54
- IEC 61010-1 (AS 61010.1) – Safety requirements for electrical equipment for measurement, control and laboratory use – Part 1: General requirements
- EN 61557-1 – Electrical safety in low voltage distribution systems up to 1000 V AC and 1500 V DC – Part 1: General requirements
- EN 61557-2 – Electrical safety in low voltage distribution systems up to 1000 V AC and 1500 V DC – Part 2: Insulation resistance
- EN 61557-4 – Electrical safety in low voltage distribution systems up to 1000 V AC and 1500 V DC – Part 4: Resistance of earth connection and equipotential bonding
- IEC 61326 – Electrical equipment for measurement, control and laboratory use – EMC requirements
- IEC 60529 (AS 60529) – Degrees of protection provided by enclosures (IP Code)


Loading…