MI-3125 Instaltest Combo – Metrel
Product Additional information
Find a store
Where to buy
Nearest Volt Safety distributors
Get in touch
Download datasheet
Product Description
The Metrel MI 3125 InstalTest COMBO is a handheld multifunction installation tester. It’s built for electricians and contractors testing low-voltage installations to AS/NZS 3000 and AS/NZS 3017. It does the work of five instruments (multimeter, insulation tester, RCD tester, loop impedance tester and phase sequence tester), covering 12 tests in one portable unit. Its single-button socket test checks socket outlets in seconds without trailing leads, and you get a clear Pass/Fail result on every test.
Key features:
Insulation resistance testing at five test voltages: 50, 100, 250, 500 and 1000 V DC.
- Up to 199.9 MΩ at 50, 100 and 250 V, with ±(5% of reading + 3 digits) accuracy up to 19.99 MΩ
- Up to 999 MΩ at 500 and 1000 V, with ±(5% of reading + 3 digits) accuracy up to 19.99 MΩ
- The actual instrument test voltage is shown alongside the result
Socket test without trailing leads:
- Earth continuity, polarity and correct connection tests with one push of a button
- Cuts socket testing from four tests to one
- Pass/Fail shown with a tick or cross on screen and a green or red LED
Earth continuity and equipotential bonding (R LOWΩ):
- Measures from 0.00 to 1999 Ω with at least 200 mA into 2 Ω. Accuracy is ±(3% of reading + 3 digits) up to 19.99 Ω, and test polarity reverses automatically.
- Test lead compensation: Compensates for lead resistance up to 5 Ω.
RCD testing:
- Five functions: contact voltage, trip time, trip current, ramp test and AUTO, which tests every RCD parameter with one button press
- Nominal residual currents of 10, 30, 100, 300, 500 and 1000 mA
- Tests AC (sine-wave) and A (pulsed) type RCDs, both G (non-delayed) and S (time-delayed)
- You can choose a starting polarity of 0° or 180°
- Trip time accuracy is ±1 ms from 0 to 40 ms
Fault loop and line impedance with prospective fault current:
- Z-loop high-current test (6.5 A for 10 ms) for circuits without RCD protection
- Zs-rcd low-current test that won’t trip the RCD
- Measures 0.00 Ω to 9.99 kΩ and calculates prospective fault current up to 23.0 kA
- You can select the fuse type, rating and tripping time
Voltage, frequency and phase rotation:
- True RMS voltage from 0 to 550 V, ±(2% of reading + 2 digits)
- Frequency measurement from 0 to 499.9 Hz
- Shows L-N, L-PE and N-PE voltages at the same time, in real time
- Phase sequence shown as 1.2.3 or 3.2.1 on three-phase systems
Pass/Fail limits: Use the preset AS/NZS 3017 limits or set your own
On-screen help: The HELP button brings up connection diagrams for each test.
Display: 128 × 64 dot-matrix display with backlight.
Power and battery life: Six 1.5 V NiMH rechargeable batteries (9 V DC) give about 20 hours of use. An AC adaptor is included.
Operating temperature: 0 to +40 °C, with relative humidity up to 95%.
Dimensions: 140 × 80 × 230 mm.
Weight: 1.0 kg without batteries.
Options:
Soft Padded Carrying Bag
Standards:
- CAT III 600 V / CAT IV 300 V
- IP40
- AS/NZS 3000 – Electrical installations (Wiring Rules)
- AS/NZS 3017 – Electrical installations – Verification guidelines